Area of refuge size and stair landing fit

Helonic is an AI construction drawing analysis platform for people check areas of refuge during plan review. The two-way phone, the clear floor space, and the stair landing have to fit on the enlarged stair plan

An area of refuge passes review when the enlarged stair plan shows one 30 by 48 inch wheelchair space for every 200 occupants served, placed outside the required egress width, next to a two-way communication device, on a stair at least 48 inches wide between handrails. Helonic checks that the refuge fits on the enlarged plan. IBC Sections 1009.3 and 1009.6 set those numbers. The miss is a refuge that is hatched on the life safety plan but does not fit once the stair, the door swing, and the handrails are drawn.

When is an area of refuge required?

IBC Section 1009 requires accessible means of egress from accessible spaces. On floors above or below the level of exit discharge, an exit stair used as an accessible means of egress has to be at least 48 inches wide between handrails. It also has to include an area of refuge on an enlarged landing, or be reached from an area of refuge or a horizontal exit.

Buildings sprinklered throughout under NFPA 13 or 13R are exempt from both the 48 inch width and the area of refuge in most cases. Check the sprinkler status on the code plan before you look for a refuge.

How big does an area of refuge have to be?

Section 1009.6.3 requires one wheelchair space, 30 by 48 inches, for every 200 occupants or portion of 200. The count is based on the occupant load of the refuge and the areas it serves. The spaces can't reduce the required egress width or capacity, and reaching any one space can't require passing through more than one other space.

Occupants servedWheelchair spaces
1 to 2001
201 to 4002
401 to 6003
601 to 8004

The refuge is separated from the rest of the floor by a smoke barrier, or it sits behind a horizontal exit, unless it is inside the stair enclosure itself. Occupant load math is in how to calculate occupant load.

How do the stair landing and the refuge compete for space?

Most refuges sit on an enlarged landing inside the stair. That landing already has to hold the stair width, the door swing, and the handrail extensions. The wheelchair space goes on top of all of that, outside the path people take down the stair. These are the conflicts that show up on the enlarged plan:

  • The stair is 44 inches wide when an accessible means of egress stair needs 48 inches between handrails.
  • The wheelchair space sits inside the landing width the stair already requires.
  • The stair door swings over the wheelchair space or cuts the landing below half its width.
  • A handrail extension or a standpipe valve projects into the space.
  • The two-way communication device is in the corridor on the electrical plan, not at the refuge.
  • There is no sign identifying the refuge on the signage drawings.

The communication device has its own page: area of refuge two-way communication covers where it goes and what it calls. Stair geometry is in stair design requirements.

How do you check an area of refuge in one pass?

  1. Check the sprinkler status on the code plan, and confirm whether refuges are required.
  2. Count the occupants each refuge serves and work out the number of wheelchair spaces.
  3. Draw the 30 by 48 inch rectangles on the enlarged plan, outside the egress path.
  4. Measure the stair clear width between handrails.
  5. Draw the stair door swing and check it against the spaces and the landing.
  6. Find the communication device and the sign at the refuge.

Drawing the required space on the plan, rather than trusting a label, is a habit that applies across how to review construction drawings.

Drawing Review Checkpoint

Draw the 30 by 48 inch rectangle on the enlarged plan yourself. A hatch labeled area of refuge says nothing about whether the space fits.

How does Helonic check areas of refuge?

Helonic reads the code plan, the enlarged stair plans, the electrical plans, and the signage drawings together. It flags a refuge whose stair is under 48 inches between handrails, a wheelchair space inside the egress width, a door swing over the space, and a refuge with no communication device. The accessibility checks cite the sheet and the grid for each finding.

Findings are decision support. The architect decides what changes. For how this review fits a project, see AI for construction drawings.

Practitioner insight

“The hatch says area of refuge, and the enlarged plan has a 44 inch stair, a 36 inch door swinging onto the landing, and nowhere left to park a wheelchair.”

Common finding in accessibility and egress drawing review.

Area of Refuge FAQs

How big does an area of refuge have to be?
IBC Section 1009.6.3 requires one 30 by 48 inch wheelchair space for every 200 occupants, or portion of 200, served by the refuge. The spaces can't reduce the required egress width.
Is an area of refuge required in a sprinklered building?
In most cases, no. Buildings sprinklered throughout under NFPA 13 or 13R are exempt from the area of refuge and the 48 inch stair width in most occupancies. Check the exceptions in Section 1009.3 for the project.
Can the wheelchair space be on the stair landing?
Yes, on an enlarged landing inside the stair enclosure, as long as the space sits outside the width the stair and landing need for egress.
How wide does a stair serving an area of refuge have to be?
At least 48 inches clear between handrails when the stair is part of an accessible means of egress and the building is not sprinklered throughout.
What else has to be at an area of refuge?
A two-way communication system, instructions, and signage identifying the refuge. The communication requirements are covered on the area of refuge two-way communication page.
MG

Manas Gandhi

Co-founder & CTO, Helonic

Manas is the co-founder and CTO of Helonic, where he leads engineering and AI research for construction drawing analysis. He works directly with structural, MEP, civil, and fire protection engineers to translate the way they review drawings into AI systems that flag the issues that actually matter in the field. Before Helonic, he built machine learning pipelines for technical document understanding and has spent the last several years interviewing licensed design engineers and discipline leads to ground product decisions in real practice rather than industry assumptions.

Areas of focus
  • AI for technical document understanding
  • Cross-discipline coordination workflows
  • Code compliance automation (IBC, NEC, NFPA, IPC, IMC, ASCE)
  • Structural and MEP drawing review systems

How this page was researched: Requirements were checked against IBC 2021 Sections 1009.3 and 1009.6 for accessible means of egress stairs and area of refuge size and separation. The two-way communication system is covered on a separate page so the two do not share a query.

Last reviewed by Manas Gandhi · October 8, 2026

Catch refuges that do not fit before issue

Helonic checks each area of refuge against the stair width, the door swing, and the wheelchair spaces it needs.