Helonic is an AI construction drawing analysis platform for people check stair pressurization during plan review. The fan, the outdoor intake, the relief, and the stair doors have to show up together on the life safety, mechanical, and electrical sheets
A pressurized stair passes review when the life safety plan, the mechanical plan, the roof plan, and the electrical sheets all show the same system: a supply fan, an outdoor air intake away from smoke sources, a way to keep the pressure in range, and stair doors that still open with the force the code allows. Helonic matches each pressurized stair to its fan, relief, and power. IBC Section 909.20 sets the pressure range. The common failure is a stair labeled pressurized on one sheet and drawn as an ordinary stair on another.
In a high-rise, IBC Section 403.5.4 requires every required interior exit stair serving floors more than 75 feet above the lowest level of fire department vehicle access to be a smokeproof enclosure. Underground buildings have a similar rule.
A smokeproof enclosure normally has a vestibule. IBC Section 909.20 lets a fully sprinklered building skip the vestibule if the stair is pressurized instead. The stair has to hold at least 0.10 inch of water (25 Pa) and no more than 0.35 inch of water (87 Pa) relative to the building, with all stair doors closed, under the worst stack and wind conditions expected.
The upper limit protects the doors. IBC Section 1010.1.3 limits the force to set a side-swinging egress door in motion to 30 pounds. Too much pressure and people on the floor can't open the stair door. If the stair uses a vestibule instead, see smokeproof stair vestibule size and door swing.
Stair pressurization crosses more disciplines than almost any other life safety system. Each row is a place where the sheets can drift apart.
| Item | Sheet | What to check |
|---|---|---|
| Supply fan | Mechanical plan, roof plan, equipment schedule | The same fan tag and location appear on all three, and the fan serves the stair the life safety plan names. |
| Outdoor intake | Roof plan | The intake sits away from exhaust outlets, generator exhaust, and smoke exhaust discharge. |
| Supply points | Mechanical plans and sections | Tall stairs usually need supply at several levels so pressure stays even from top to bottom. |
| Pressure control | Mechanical plan and sequence | A relief damper, a variable speed drive, or another control keeps the stair below 0.35 inch. |
| Stair doors | Door schedule and hardware sets | The undercut, gaskets, and closers match the leakage the pressurization design assumed. |
| Start and power | Fire alarm matrix and electrical one-line | The fire alarm starts the fan, and the fan and its controls are on standby power. |
Smoke control systems also get special inspection and testing under IBC Section 1705, so a mismatch caught in plan review is far cheaper than one caught at the pressure test. The broader habit is described in how to review construction drawings.
Ask for the pressurization calculation or design narrative. If it assumes small door gaps and the door schedule says something else, the pressure test at the end of the job is the first time anyone finds out.
Helonic matches each pressurized stair on the life safety plan to a fan on the mechanical and roof plans, a start signal on the fire alarm matrix, and standby power on the electrical sheets. It flags a stair with no fan, a fan with no relief, or an intake drawn beside an exhaust. The fire and life safety checks cite the sheet for each finding.
Findings are decision support. The mechanical engineer of record decides what changes. For how this review fits a project, see AI for construction drawings.
Practitioner insight
“The fan shows up on the roof plan, but nobody checks the door schedule. The calc assumed tight doors, the doors arrive with a big undercut, and the stair never reaches 0.10 inch at the test.”
Common finding in high-rise life safety and mechanical coordination review.
Manas is the co-founder and CTO of Helonic, where he leads engineering and AI research for construction drawing analysis. He works directly with structural, MEP, civil, and fire protection engineers to translate the way they review drawings into AI systems that flag the issues that actually matter in the field. Before Helonic, he built machine learning pipelines for technical document understanding and has spent the last several years interviewing licensed design engineers and discipline leads to ground product decisions in real practice rather than industry assumptions.
How this page was researched: Requirements were checked against IBC 2021 Sections 403.5.4, 909.20, and 1010.1.3, and the IBC Section 1705 special inspection requirements for smoke control systems.
Last reviewed by Manas Gandhi · October 6, 2026
Related references for life safety and mechanical coordination.
The vestibule option for smokeproof enclosures.
Stair geometry, landings, and handrails.
Fans, ducts, and dampers on the mechanical sheets.
Dampers that work with the smoke control system.
Where undercuts, gaskets, and closers are specified.
A systematic approach to catching drawing errors before construction.