An exit passageway passes review when it stays a rated enclosure from end to end, its only openings and penetrations are the ones IBC Section 1024 allows, and nothing along the way cuts the required width. Helonic flags anything that breaks the enclosure. The passage carries at least the rating of the stair it extends, often 2 hours. Most misses happen when a tenant plan or a later revision adds an ordinary door, a duct, or a closet that opens into the passage.
An exit passageway is an exit that runs horizontally. It most often carries an interior exit stair from where it lands to the outside or to a public way. IBC Section 1024 covers it.
The passage is built with fire barriers, horizontal assemblies, or both, rated at least 1 hour and not less than the rating of any interior exit stair it connects to. Its width is at least 44 inches, or 36 inches where it serves fewer than 50 occupants, and never less than the capacity the occupant load requires. It ends at an exit discharge or a public way.
Where the passage extends a stair, Section 1023.3.1 puts a rated fire door between the stair and the passage. The egress basics page explains how exits, exit access, and exit discharge fit together.
Section 1024.5 limits openings to those needed for exit access from normally occupied spaces and for leaving the passage. Elevators can't open into it. A storage room, an electrical room, or a janitor closet is not a normally occupied space, so a door from one of them into the passage is a problem. Every opening that is allowed gets a rated, self-closing door.
Section 1024.6 limits penetrations to a short list:
A duct main, a domestic water line, or a conduit run that serves the tenant next door can't cross the passage. Listed firestop systems at the allowed penetrations are covered in the firestopping guide.
| Item | Sheet | What to check |
|---|---|---|
| Enclosure | Architectural plans and wall-type legend | The rating matches the stair it extends, and the walls run to the deck or to a rated lid. |
| Doors | Architectural plans and door schedule | Only doors from normally occupied spaces, each rated and self-closing. |
| Width | Enlarged plan | At least 44 inches clear, and door swings stay within the encroachment limits. |
| Penetrations | Mechanical, plumbing, and electrical plans | Only the items Section 1024.6 allows cross the enclosure. |
| Termination | Ground floor and site plans | The passage ends at an exterior exit discharge or a public way. |
| Tenant work | Tenant improvement drawings | Later tenant sets do not add doors or penetrations the base building never had. |
Tenant work is the biggest source of drift. The tenant improvement as-built risk page covers why the base building drawings stop matching the space.
Reading one exit through every discipline is the core of how to review construction drawings.
Check the tenant improvement drawings against the base building. The shell set usually gets the passage right, and the first tenant revision is where a door shows up.
Helonic reads the passage across the architectural, mechanical, plumbing, and electrical sheets. It flags a wall rated below the stair, a door from a storage or service room, and a duct or pipe that does not belong in the enclosure. The egress compliance checks cite the sheet and the grid for each finding.
Findings are decision support. The architect decides what changes. For how this review fits a project, see AI for construction drawings.
Practitioner insight
“The base building passage is clean. Then the tenant set adds a stockroom door and a duct to a rooftop unit, and nobody pulls the shell drawings to compare.”
Common finding in retail and mixed-use egress review.
Manas is the co-founder and CTO of Helonic, where he leads engineering and AI research for construction drawing analysis. He works directly with structural, MEP, civil, and fire protection engineers to translate the way they review drawings into AI systems that flag the issues that actually matter in the field. Before Helonic, he built machine learning pipelines for technical document understanding and has spent the last several years interviewing licensed design engineers and discipline leads to ground product decisions in real practice rather than industry assumptions.
How this page was researched: Requirements were checked against IBC 2021 Section 1024 for exit passageway width, construction, openings, and penetrations, and Section 1023.3.1 for stair extensions.
Last reviewed by Manas Gandhi · October 8, 2026
Related references for egress and life safety review.
Exits, exit access, and exit discharge.
A full egress review on a drawing set.
Another exit that works on a single floor.
Listed systems at the penetrations the code allows.
Where exit passageways are shown and labeled.
A systematic approach to catching drawing errors before construction.