IBC egress widths are calculated using two factors, 0.3" per person for stairways and 0.2" per person for other egress components, applied to occupant load. Here's the full calculation method with the minimum-width floors that override the math.
Per IBC Section 1005.3.1, required egress width = occupant load × 0.3" (for stairways, sprinklered building) or × 0.2" (for corridors, doors, and other level components). If the building is not fully sprinklered, the factors increase to 0.5" and 0.3" respectively (IBC 1005.3.2). Minimum absolute widths still apply even if the calculation is smaller.
A 200-occupant floor needs 40" of stair width (200 × 0.2" in a sprinklered building per 1005.3.1), but the minimum stair width is 44" per IBC 1011.2. The minimum wins. Drawing reviews that apply only the calculation miss the floor requirements and get AHJ corrections.
Regardless of calculated width, minimums apply:
When two or more exits are provided, the total egress capacity must be arranged so that the loss of one exit does not leave the remaining exits with less than 50% of the required capacity. In practice, no single exit can serve more than 50% of the occupant load in a two-exit configuration.
For a 300-occupant floor with three exits, each exit needs egress capacity for 150 occupants (50% × 300), not 100 (300 ÷ 3). Drawing review should verify the exit assignment in the occupant-load schedule.
When egress paths converge, such as where upstairs occupants enter a stair already carrying downstairs occupants, the egress width must account for the combined load. The stair width from that level down must be the greater of either floor's requirement plus the convergence load.
This applies at stair merging, corridor junctions, and at the level-of-exit-discharge. Many code reviewers miss this because the calculation is not done floor-by-floor in a naive schedule.
Egress width is paired with travel distance:
These numbers drive exit placement and affect overall egress calculation as much as width does. Review both together on the life safety plan.
Classroom floor in a sprinklered Group E school, occupant load 450:
For assembly occupancies, start with our occupant load calculation.
More IBC and life safety references for plan review.